26 How to Install Your Analog Module
Wiring to a 1794-TBN or 1794-TBNF Terminal Base Unit
1. Connect individual input or output wiring to the even numbered
terminals on row (B) as indicated in the table below.
2. Connect the associated return wiring to the corresponding odd
numbered terminal on row (C) for each input or output as
indicated in the table below.
3. Connect 24V dc to terminal 34 on row (C).
4. Connect 24V dc common to terminal 16 on row (B).
5. If continuing power to the next terminal base unit, connect a
jumper from terminal 51 (24V dc) on this base unit to terminal
34 on the next base unit.
If continuing common to the next terminal base unit, connect a
jumper from terminal 33 (24V dc common) on this base unit to termi-
nal 16 on the next base unit.
0
2
4
6
8
10
12
14
33
16
1
3
5
7
9
11
13
15
51
34
16, 0, 2, 4, 6,
8, 10, 12, 14, 33
34, 1, 3, 5, 7,
9, 11, 13, 15, 51
C
B
1794-TBN, 1794-TBNF
16
33
Even Numbered Terminals 0 thru 14
34
51
Odd Numbered Terminals 1 thru 15
Table 2.1
Wiring connections for 1794-TB3, -TB3T, -TB3S, -TB3TS, -TBN and -TBNF Terminal Base
Units when using the 1794-IF4I or 1794-OF4I Isolated Analog Module
Channel
Signal Type
Label Markings
1794-TB3, -TB3T
1
, -TB3S, -TB3TS
(2)
1794-TBN, 1794-TBNF
Signal
Terminal
Signal Return
0
Current
I0
0
Current
I0 Ret
1
Voltage
V0
2
Voltage
V0 Ret
3
1
Current
I1
4
Current
I1 Ret
5
Voltage
V1
6
Voltage
V1 Ret
7