26 How to Install Your Analog Module

Wiring to a 1794-TBN or 1794-TBNF Terminal Base Unit

1. Connect individual input or output wiring to the even numbered

terminals on row (B) as indicated in the table below.

2. Connect the associated return wiring to the corresponding odd

numbered terminal on row (C) for each input or output as
indicated in the table below.

3. Connect 24V dc to terminal 34 on row (C).

4. Connect 24V dc common to terminal 16 on row (B).

5. If continuing power to the next terminal base unit, connect a

jumper from terminal 51 (24V dc) on this base unit to terminal
34 on the next base unit.

If continuing common to the next terminal base unit, connect a
jumper from terminal 33 (24V dc common) on this base unit to termi-

nal 16 on the next base unit.

0

2

4

6

8

10

12

14

33

16

1

3

5

7

9

11

13

15

51

34

16, 0, 2, 4, 6,
8, 10, 12, 14, 33

34, 1, 3, 5, 7,
9, 11, 13, 15, 51

C

B

1794-TBN, 1794-TBNF

16

33

Even Numbered Terminals 0 thru 14

34

51

Odd Numbered Terminals 1 thru 15

Table 2.1

Wiring connections for 1794-TB3, -TB3T, -TB3S, -TB3TS, -TBN and -TBNF Terminal Base
Units when using the 1794-IF4I or 1794-OF4I Isolated Analog Module

Channel

Signal Type

Label Markings

1794-TB3, -TB3T

1

, -TB3S, -TB3TS

(2)

1794-TBN, 1794-TBNF

Signal
Terminal

Signal Return

0

Current

I0

0

Current

I0 Ret

1

Voltage

V0

2

Voltage

V0 Ret

3

1

Current

I1

4

Current

I1 Ret

5

Voltage

V1

6

Voltage

V1 Ret

7