Adapter Input Status Word
The input status word consists of:
•
I/O module fault bits – 1 status bit for each slot
•
node address changed – 1 bit
•
I/O status – 1 bit
The adapter input status word bit descriptions are shown in the
following table.
15
Bit:
0
1
2
3
4
5
6
7
8
10 through 15
I/O Module Fault Bits
Node Address Changed Bit
Slot 0
Slot 1
Slot 2
Slot 3
Slot 4
Slot 5
Slot 6
Slot 7
9
I/O State Bit
Not Used
Bit Description
Bit
Explanation
I/O Module Fault
0
This bit is set (1) when an error is detected in slot position 0.
1
This bit is set (1) when an error is detected in slot position 1.
2
This bit is set (1) when an error is detected in slot position 2.
3
This bit is set (1) when an error is detected in slot position 3.
4
This bit is set (1) when an error is detected in slot position 4.
5
This bit is set (1) when an error is detected in slot position 5.
6
This bit is set (1) when an error is detected in slot position 6.
7
This bit is set (1) when an error is detected in slot position 7.
Node Address Changed
8
This bit is set (1) when the node address switch setting has been
changed since power up.
I/O State
9
Bit = 0 – idle
Bit = 1 – run
10 – 15 Not used – sent as zeroes.