Time delay for a/d conversion, Response to slot disable – Rockwell Automation 1746-FIO4V SLC 500 Fast Analog I/O/ User Manual User Manual
Page 37
![background image](/manuals/579225/37/background.png)
Publication 1746-UM009B-EN-P - September 2007
Processor and Module Considerations 37
Time Delay for A/D Conversion
The A/D converter uses 7.5 µs for data conversion, 248.5 µs for data
settling, and 256 µs for data transfer to the backplane. New data is
available in 512 µs cycles.
Response Time of A/D Converter
The worst-case specification for the SLC processor to read a step
change is 1.1ms between readings. This is true for a step change
occurring just after data conversion (first 7.5 µs of the 512 µs cycle). In
this case, the read cycle cannot begin until the next data conversion.
Response to Slot Disable
You can disable any I/O rack slot by means of a processor function.
Before disabling a slot containing an analog I/O module, be aware of
the implications.
Data ready for
processor read
Data
conversion
Data
settling
Data transfer to
the backplane
Start
7.5 µs
248.5 µs
256 µs
512 µs
Worst case point for a change of input to occur.
This results in a 1.1ms delay for the processor to read a step change.
IMPORTANT
Do not attempt to read data from the module more often than
once every 512 µs. If you do, the module may not be able to
update new data.
ATTENTION
Clearly understand the safety implications of disabling an
analog module slot before doing it.