Rockwell Automation 1606-XLS960FE Power Supply Reference Manual User Manual
Page 7
All parameters are specified at 48V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM018A-EN-P — February 2014
7
Bulletin 1606 Switched Mode Power Supplies
Fig. 6-1
Output voltage vs. output current in
“single use” mode, typ.
Fig. 6-2
Output voltage vs. output current in
“parallel use” mode, typ.
Output Voltage
0
0
5
10
15
20
8
16
24
56V
32
40
48
30
25
35A
Output Current
Adjustment Range
Hiccup
mode
A
B
A
B
Short-term (4s)
then switching
to curve
Continuously
available
A
A
B
Output Voltage (Parallel Use, typ.)
42V
0
10
20
44V
46V
48V
56V
50V
52V
54V
30A
25
15
5
Adjustment Range
Factory
setting
Continuously
allowed
Bonus
Power
Output Current
Fig. 6-3
Short-circuit on output, Hiccup
PLUS
mode, typ.
Fig. 6-4
Dynamic overcurrent capability, typ.
Output
Current
0
35A
17s
17s
17s
2s
2s
2s
t
Short -circuit
Normal
operation
Normal
operation
Output Voltage (dynamic behavior, < 25ms)
0
0
8
16
24
54V
32
40
48
70A
30
60
10
20
40
50
Adjustment
Range
Output Current
Fig. 6-5
Bonus time vs. output power
Fig. 6-6
BonusPower recovery time
max.
Bonus Time
0
100
120
130
140
150
170%
1
2
3
4
5s
110
160
Output Power
min.
Power
Demand
100%
t
t
Limitation by
Power Manager
Output
Voltage
Bonus Power disabled
Bonus
Time
Recovery Time
BonusPower is available as soon as power comes on and after the end of an output short circuit or output
overload.
Fig. 6-7
BonusPower after input turn-on
Fig. 6-8
BonusPower after output short
100%
Output
Voltage
Input
Voltage
Bonus
Power
Output
Power
150%
Short of
Output
100%
Output
Voltage
Bonus
Power
Output
Power
150%