beautypg.com

Parallel use to increase output power, Parallel use for redundancy – Rockwell Automation 1606-XLS960FE Power Supply Reference Manual User Manual

Page 24

background image

All parameters are specified at 48V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.

24

Rockwell Automation Publication 1606-RM018A-EN-P — February 2014

Bulletin 1606 Switched Mode Power Supplies

25.6. Parallel Use to Increase Output Power

Unit A

AC

DC

Unit B

AC

DC

-

+

-

+

Load

+

-

Power supplies from the same series can be used in parallel to increase
the output power. The output voltage shall be adjusted to the same value
(±100mV) in “Single use” mode with the same load conditions on all units, or
the units can be left with the factory settings. After the adjustments, the
jumper on the front of the unit shall be moved from “Single use” to “Parallel
use”, in order to achieve load sharing. The “Parallel use” mode regulates the
output voltage in such a manner that the voltage at no load is approx. 4%
higher than at nominal load. See also section 6. If no jumper is plugged in, the
unit is in “Single use” mode. Factory setting is also “Single use” mode.

If you connect more than three units in parallel, a fuse or circuit breaker with a rating of 30A or 32A is required on
each output. Alternatively, a diode or redundancy module can also be used.

Energize all units at the same time to avoid the overload Hiccup

PLUS

mode. It also might be necessary to cycle the input

power (turn-off for at least five seconds), if the output was in Hiccup

PLUS

mode due to overload or short circuits and the

required output current is higher than the current of one unit.

Keep an installation clearance of 15mm (left / right) between two power supplies and avoid installing the power
supplies on top of each other. Do not use power supplies in parallel in mounting orientations other than the standard
mounting orientation (terminals on the bottom of the unit) or in any other condition where a derating of the output
current is required (e.g. altitude, above 60°C, …).

Please note that leakage current, EMI, inrush current, harmonics will increase when using multiple power supplies.

25.7. Parallel Use for Redundancy

Power supplies can be paralleled for redundancy to gain higher system availability. Redundant systems require a
certain amount of extra power to support the load in case one power supply unit fails. The simplest way is to put two
power supplies in parallel. This is called a 1+1 redundancy. In case one power supply unit fails, the other one is
automatically able to support the load current without any interruption. Redundant systems for a higher power
demand are usually built in a N+1 method. E.g. five power supplies, each rated for 20A are paralleled to build a 80A
redundant system. For N+1 redundancy the same restrictions apply as for increasing the output power, see also
section 25.6.

Please note: This simple way to build a redundant system does not cover failures such as an internal short circuit in
the secondary side of the power supply. In such a case, the defective unit becomes a load for the other power supplies
and the output voltage can no longer be maintained. You can avoid this by using redundancy modules including
decoupling devices (diodes or mosfets). Further information and wiring configurations can be found in section 24.3.

Recommendations for building redundant power systems:

a)

Use separate input fuses for each

power supply. A separate source for each supply when possible increases the

reliability of the redundant system.

b)

Set the power supply into “Parallel Use” mode.

c)

Monitor the individual power supply units. Therefore, use the DC-OK relay contact of the 1606-XLS power supply.

d) We recommend setting the output voltages of all units to the same value (± 100mV) or leaving it on the factory
setting.