Efficiency and power losses – Rockwell Automation 1606-XLS960FE Power Supply Reference Manual User Manual
Page 11
All parameters are specified at 48V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM018A-EN-P — February 2014
11
Bulletin 1606 Switched Mode Power Supplies
12. Efficiency and Power Losses
AC 230V
Efficiency
typ.
95.0%
at 48V, 20A
Average efficiency
*)
typ.
94.2%
25% at 5A, 25% at 10A, 25% at 15A. 25% at 20A
Power losses
typ.
3.2W
with activated shut-down
typ.
12.0W
at
48V,
0A
(no
load)
typ.
30.1W
at 48V, 10A (half load)
typ.
50.5W
at
48V,
20A
(full
load)
*) The average efficiency is an assumption for a typical application where the power supply is loaded with 25% of the nominal load for 25%
of the time, 50% of the nominal load for another 25% of the time, 75% of the nominal load for another 25% of the time and with 100%
of the nominal load for the rest of the time.
Fig. 12-1
Efficiency vs. output current at 48V,
typ.
Fig. 12-2
Losses vs. output current at 48V,
typ.
Efficiency
4
6
8
10
12
14
16
18 20A
91
92
93
Output Current
94
95%
Power Losses
0
2
4
6
8 10 12 14
20A
10
0
30
40
50
60W
16 18
20
Output Current
Fig. 12-3
Efficiency vs. input voltage at 48V,
20A, typ.
Fig. 12-4
Losses vs. input voltage at 48V, 20A,
typ.
Efficiency
170
190
210
230
250 270Vac
93
94
95
Input Voltage
96%
Power Losses
30
35
40
45
50
55
60W
170
190
210
230
250 270Vac
Input Voltage