beautypg.com

Efficiency and power losses – Rockwell Automation 1606-XLS960FE Power Supply Reference Manual User Manual

Page 11

background image

All parameters are specified at 48V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.

Rockwell Automation Publication 1606-RM018A-EN-P — February 2014

11

Bulletin 1606 Switched Mode Power Supplies

12. Efficiency and Power Losses

AC 230V

Efficiency

typ.

95.0%

at 48V, 20A

Average efficiency

*)

typ.

94.2%

25% at 5A, 25% at 10A, 25% at 15A. 25% at 20A

Power losses

typ.

3.2W

with activated shut-down

typ.

12.0W

at

48V,

0A

(no

load)

typ.

30.1W

at 48V, 10A (half load)

typ.

50.5W

at

48V,

20A

(full

load)

*) The average efficiency is an assumption for a typical application where the power supply is loaded with 25% of the nominal load for 25%

of the time, 50% of the nominal load for another 25% of the time, 75% of the nominal load for another 25% of the time and with 100%
of the nominal load for the rest of the time.

Fig. 12-1

Efficiency vs. output current at 48V,

typ.

Fig. 12-2

Losses vs. output current at 48V,

typ.

Efficiency

4

6

8

10

12

14

16

18 20A

91

92

93

Output Current

94

95%

Power Losses

0

2

4

6

8 10 12 14

20A

10

0

30

40

50

60W

16 18

20

Output Current

Fig. 12-3

Efficiency vs. input voltage at 48V,

20A, typ.

Fig. 12-4

Losses vs. input voltage at 48V, 20A,

typ.

Efficiency

170

190

210

230

250 270Vac

93

94

95

Input Voltage

96%

Power Losses

30

35

40

45

50

55

60W

170

190

210

230

250 270Vac

Input Voltage