Front side and user elements – Rockwell Automation 1606-XLS960FE Power Supply Reference Manual User Manual
Page 14
![background image](/manuals/578789/14/background.png)
All parameters are specified at 48V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
14
Rockwell Automation Publication 1606-RM018A-EN-P — February 2014
Bulletin 1606 Switched Mode Power Supplies
16. Front Side and User Elements
Fig. 16-1
Front side
A Input
Terminals (Screw terminals)
N,
L Line input
...PE (Protective Earth) input
B Output
Terminals (Screw terminals, two pins per pole)
+ Positive output
– Negative (return) output
C “Parallel Use” “Single Use” Selector
Set jumper to “Parallel Use” when power supplies are
connected in parallel to increase the output power. In order
to achieve a sharing of the load current between the
individual power supplies, the “parallel use” regulates the
output voltage in such a manner that the voltage at no load
is approx. 4% higher than at nominal load. See also section
25.6. A missing jumper is equal to a “Single Use” mode.
D Output Voltage Potentiometer
Multi turn potentiometer;
Open the flap to set the output voltage.
Factory set: 48.0V at full output current, “Single Use” mode.
E DC-OK
LED
(green)
On, when the voltage on the output terminals is >90% of the
adjusted output voltage
F Overload
LED
(red)
- On, when the voltage on the output terminals is <90% of
the adjusted output voltage, or in case of a short circuit in
the output.
- Flashing,
when the shut-down has been activated or the
unit has switched off due to over-temperature.
- Input voltage is required
G DC-OK
Relay
Contact
The DC-OK relay contact is synchronized with the DC-OK LED.
See section 8 for details.
H Shut-down
Input
Allows the power supply to be shut down. Can be activated
with a switch contact or an external voltage.
Indicators, LEDs
Overload LED
DC-OK LED
DC-OK Contact
Normal mode
OFF
ON
Closed
During BonusPower
OFF
ON
Closed
Overload (Hiccup mode)
flashing
OFF
Open
Output short circuit
flashing
OFF
Open
Temperature Shut-down
flashing
OFF
Open
Active Shut-down input
flashing
OFF
Open
No input power
OFF
OFF
Open