Ac input – Rockwell Automation 1606-XLS960FE Power Supply Reference Manual User Manual
Page 4
All parameters are specified at 48V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
4
Rockwell Automation Publication 1606-RM018A-EN-P — February 2014
Bulletin 1606 Switched Mode Power Supplies
3. AC Input
AC input
nom.
AC 200-240V
suitable for TN, TT and IT mains networks
AC input range
min.
170-264Vac
continuous operation
min.
110-170Vac
full
power
for
up
to
200ms
min.
0-170Vac
no damage to the unit
264-300Vac
<
500ms
Allowed voltage L or N to earth
max.
300Vac
continuous, IEC 62103
Input frequency
nom.
50–60Hz
±6%
Turn-on voltage
typ.
164Vac
steady-state value, load independent, see Fig. 3-1
Shut-down voltage
typ.
151Vac
steady-state value, load independent, see Fig. 3-1
Input current
typ.
4.6A
at 48V, 20A, see Fig. 3-3
Power factor
*)
typ.
0.96
at 48V, 20A, see Fig. 3-4
Crest factor
**)
typ.
1.65
at
48V,
20A
Start-up delay
typ.
750ms
see Fig. 3-2
Rise time
typ.
18ms
at 48V, 20A, resistive load, 0mF see Fig. 3-2
typ.
35ms
at 48V, 20A, resistive load, 20mF see Fig. 3-2
Turn-on overshoot
max.
200mV
see Fig. 3-2
*)
The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Fig. 3-1
Input voltage range
Fig. 3-2
Turn-on behavior, definitions
Turn-on
170V
Rated input range
V
IN
P
OUT
151V
264Vac
Shut
-down
164V
Start-up
delay
Rise
Time
Ov
ersh
oot
- 5%
Output
Voltage
Input
Voltage
Fig. 3-3
Input current vs. output load at 48V
Fig. 3-4
Power factor vs. output load at 48V
20A
2
4
6
8
10 12 14 16 18
0
1
2
3
4
5
6A
Input Current, typ.
Output Current
Power Factor, typ.
2
4
6
8 10 12 14 16 18 20A
0.75
0.80
0.85
0.90
0.95
1.00
Output Current