Output – Rockwell Automation 1606-XLS960FE Power Supply Reference Manual User Manual
Page 6
All parameters are specified at 48V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
6
Rockwell Automation Publication 1606-RM018A-EN-P — February 2014
Bulletin 1606 Switched Mode Power Supplies
6. Output
Output voltage
nom.
48V
Adjustment range
min.
48-54V
guaranteed
max.
56V
****)
at clockwise end position of potentiometer
Factory setting
typ.
48.0V
±0.2%, at full load, cold unit, in “single use” mode
typ.
46.0V
±0.2%, at full load, cold unit, in “parallel use” mode
typ.
48.0V
at no load, cold unit, in “parallel use” mode
Line regulation
max.
10mV
170-264Vac
Load regulation
max.
50mV
in “single use” mode: static value, 0A 20A, see Fig. 6-1
typ.
2000mV
in “parallel use” mode: static value, 0A 20A,
see Fig. 6-2
Ripple and noise voltage
max.
150mVpp
20Hz to 20MHz, 50Ohm
Output current
nom.
20A
continuously available at 48V, see Fig. 6-1 and Fig. 6-2
nom.
17.8A
continuously available at 54V, see Fig. 6-1 and Fig. 6-2
nom.
30A
short
term
available
BonusPower
®*)
, at 48V
for typical 4s, see Fig. 6-1 and Fig. 6-2
nom.
26.7A
short
term
available
BonusPower
®*)
, at 54V
for typical 4s, see Fig. 6-1 and Fig. 6-2
typ.
55A
up to 25ms, output voltage stays above 40V, see Fig.
6-4, This peak current is available once every second.
See section 25.2 for more peak current measurements.
Output power
nom.
960W
continuously available at 48-54V
nom.
1440W
*)
short
term
available
BonusPower
*)
at 48-54V
BonusPower
time
typ.
4s
duration until the output voltage dips, see Fig. 6-5
BonusPower
recovery time
typ.
7s
overload free time to reset power manager, see Fig. 6-6
Overload behavior
cont. current
output voltage > 40Vdc, see Fig. 6-1
Hiccup
PLUS
mode
**)
output voltage < 40Vdc, see Fig. 6-1
Short-circuit current
min.
30A
***)
load impedance 50mOhm, see Fig. 6-3
max.
35A
***)
load impedance 50mOhm, see Fig. 6-3
max.
11.5A
average (R.M.S.) current, load impedance 50mOhm, see
Fig. 6-3
min.
55A
up to 25ms, load impedance <10mOhm, see Fig. 6-4
typ.
63A
up to 25ms, load impedance <10mOhm, see Fig. 6-4
Output capacitance
typ.
3 700μF
included in the power supply
*)
BonusPower, short term power capability (up to typ. 4s)
The power supply is designed to support loads with a higher short-term power requirement without damage or shutdown. The short-
term duration is hardware-controlled by an output power manager. BonusPower is repeatedly available. Detailed information
can be found in section 25.1. If the power supply is loaded with the BonusPower longer than shown in the Bonus-time diagram (see
Fig. 6-5), the max. output power is automatically reduced to 960W. If the power requirement is continuously above 960W and the
voltage falls below approx. 40V (due to the current regulating mode at overload), the unit shuts-off and makes periodical restart
attempts. This behavior is called hiccup mode which is described below. If the voltage is above 40V, the unit continuously delivers
current.
**)
Hiccup
PLUS
Mode
Up to 4s of overloading, the power supply delivers continuous output current. After this, the output power is reduced to nearly zero
for approx. 17s before a new start attempt is automatically performed. If the overload has been cleared, the device will operate
normally. If the overload still exists, the output current will be delivered for 2 to 4s (depending on the overload) again followed by a
17s rest time. This cycle is repeated as long as the overload exists. See Fig. 6-3. During the off-period a small rest voltage and rest
current is present on the output.
***) Discharge
current
of
output capacitors is not included.
****) This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. There is
no guarantee this value can be achieved. The typical value is about 55V.