beautypg.com

Rockwell Automation 1512A MV Controllers - 800A One-High Cabinet User Manual

Page 59

background image

Maintenance 5-11

1512A-UM102B-EN-P – June 2013

To avoid shock hazards, lock out incoming power

(see page 5-3) before working on the equipment.

Verify with a hot stick or appropriate voltage

measuring device that all circuits are voltage free.

Failure to do so may result in severe burns, injury or

death.

1) Complete the Power Lockout Procedure (see Page 5-3).
2) Open the medium voltage door. Use the Door Interlock

Circumvention procedure described on page 5-2 to move the

isolation switch handle halfway between the OFF and ON position

(see Figure 5.8). Keep the handle in this position until the

adjustment procedure is completed.

3) With the contactor in the OFF position, insert a 0.060 in. (1.5 mm)

feeler gauge in the gap between the interlock lever and the

isolation switch operating lever. The gap must be between 0.039 in.

to 0.078 in. (1.0 mm to 2.0 mm).

4) To reduce the gap distance, follow steps 5-7.

To increase the gap distance follow steps 8-10.

Figure 5.9 – Isolation Switch Handle Adjustments

A T T E N T I O N

A T T E N T I O N

Contactor Interlock Rod Adjust-

ment