Common Installation 4-7

1512A-UM102B-EN-P – June 2013

A T T E N T I O N

A T T E N T I O N

Some control circuit configurations may require
control jumpers to let the contactor close during

the test procedure. Do not jumper any isolation

switch contacts such as ISa or ISb (see page 5-12,
figure 5.18, for the location of these contacts).

Using jumpers for these contacts may result in

equipment damage or injury to personnel.


2) Electrically operate the contactor several times. Inspect the armature

plate to verify that it fully contacts the magnetic cores.

3) Turn the selector switch to the OFF position and unplug the test

voltage.

4)

Remove any metal filings or loose hardware from around the
magnetic cores of the vacuum contactor. The debris is attracted to

the coil once it is energized and could prevent the contactor from
closing properly.