PowerFlex 755 IP00, NEMA/UL Open Type Drive
TB1 Terminal Designations
TB2 Terminal Designations (2 Relay Outputs: 2R)
Terminal
Name
Description
Related
Param
(5)
(5) I/O Module parameters will also have a Port designation.
Sh
Shield
Terminating point for wire shields when an
EMC plate or conduit box is not installed.
Sh
Ptc–
Motor PTC (–)
Motor protection device (Positive
Temperature Coefficient).
40
on Port X
Ptc+
Motor PTC (+)
Ao0–
Analog Out 0 (–)
Bipolar, ±10V, 11 bit & sign, 2 k ohm
minimum load.
4-20 mA, 11 bit & sign, 400 ohm maximum
load.
75
on Port X
Ao0+
Analog Out 0 (+)
Ao1–
Analog Out 1 (–)
85
on Port X
Ao1+
Analog Out 1 (+)
–10V
–10 Volt Reference
2k ohm minimum.
10VC
10 Volt Common
For (–) and (+) 10 Volt references.
+10V
+10 Volt Reference
2k ohm minimum.
Ai0–
Analog Input 0 (–)
Isolated
(3)
, bipolar, differential, 11 bit &
sign.
Voltage Mode: ±10V @ 88k ohm input
impedance.
Current Mode: 0-20 mA @ 93 ohm input
impedance.
(3) Differential Isolation - External source must be maintained at less than 160V with respect to PE. Input provides high common mode
immunity.
50, 70
on Port X
Ai0+
Analog Input 0 (+)
Ai1–
Analog Input 1 (–)
60, 70
on Port X
Ai1+
Analog Input 1 (+)
24VC
24 Volt Common
(1)
(1) Not present on 120V versions.
Drive supplied logic input power.
200 mA max. per I/O module
600 mA max per drive
+24V
+24 Volt DC
Di C
Digital Input Common
Common for Digital Inputs 0…5
Di 0
Digital Input 0
(2)
(2) Digital Inputs are either 24 Volts DC (2262C) or 115 Volts AC (2262D) based on module catalog number. Ensure applied voltage is
correct for I/O module.
24V DC - Opto isolated
Low State: less than 5V DC
High State: greater than 20V DC 11.2 mA DC
115V (132V Max) AC, 50/60 Hz
(4)
- Opto
isolated
Low State: less than 30V AC
High State: greater than 100V AC
(4) For CE compliance use shielded cable. Cable length should not exceed 30 m (98 ft).
1
on Port X
Di 1
Di 2
Di 3
Di 4
Di 5
Relay Out
Terminal
Name
Description
Related
Param
R0NO
Relay 0 N.O.
Relay Normally Open contact output:
240V AC, 24V DC, 2 A max.
General Purpose (Inductive) / Resistive
Relay Normally Closed contact output:
240V AC, 24V DC, 2 A max.
Resistive Only
10, 100,
101, 105,
106
on Port X
R0C
Relay 0 Common
R0NC
Relay 0 N.C.
R1NO
Relay 1 N.O.
20, 110,
111, 115,
116
on Port X
R1C
Relay 1 Common
R1NC
Relay 1 N.C.
Sh
Sh
PTC–
PTC+
Ao0–
Ao0+
Ao1–
Ao1+
–10V
10VC
+10V
Ai0–
Ai0+
Ai1–
Ai1+
24VC
+24V
DiC
Di0
Di1
Di2
Di3
Di4
Di5
R0NO
R0C
R0NC
R1NO
R1C
R1NC