Catalog number explanation – Rockwell Automation 20G PowerFlex 755 IP00 NEMA/UL Open Drive - Frames 8-10 User Manual
Page 5

Rockwell Automation Publication 750-IN020C-EN-P - May 2012
5
PowerFlex 755 IP00, NEMA/UL Open Type Drive
Catalog Number Explanation
Position
1…3
4
5
6
7
8…10
11
12
13
14
15
16
17
18
20G
1
1
T
D
485
A
N
0
N
N
N
N
N
a
b
c
d
e
f1…f2
g
h
a
Drive
Code
Type
20G
PowerFlex 755
b
Future Use
c
Input Type
Code
Description
1
AC Input w/Precharge
4
DC Input w/Precharge
d
Enclosure
Code
Description
T
IP00, UL Open Type without Control POD
e
Voltage Rating
Code
Voltage
C
400V AC / 540V DC
D
480V AC / 650V DC
E
600V AC / 810V DC
F
690V AC / 932V DC (not UL listed)
f1
ND Rating
400V AC / 540V DC, 50 Hz Input
Code
Amps
kW
Quantity
Required
Equivalent
Frame Size
C460
460
250
1
8
C540
540
315
1
C567
567
315
1
C650
650
355
1
C750
750
400
1
C770
770
400
1
C460
910
500
2
9
C540
1040
560
2
C567
1090
630
2
C650
1175
710
2
C750
1465
800
2
C770
1480
850
2
C567
1590
900
3
10
C770
2150
1250
3
To achieve the extended ratings listed for Frames 9 and 10, the base
Frame 8 drive must be paralleled 2 or 3 times. Refer to the Drive
Rating tables on pages 8, 9, 12, and 13 for detailed information.
f2
ND Rating
480V AC / 650V DC, 60 Hz Input
Code
Amps
Hp
Quantity
Required
Equivalent
Frame Size
D430
430
350
1
8
D485
485
400
1
D545
545
450
1
D617
617
500
1
D710
710
600
1
D740
740
650
1
D430
800
700
2
9
D485
960
800
2
D545
1045
900
2
D617
1135
1000
2
D710
1365
1100
2
D740
1420
1250
2
D545
1525
1350
3
10
D740
2070
1750
3
To achieve the extended ratings listed for Frames 9 and 10, the base
Frame 8 drive must be paralleled 2 or 3 times. Refer to the Drive
Rating tables on pages 8, 9, 12, and 13 for detailed information.
f3
ND Rating
600V AC / 810V DC, 60 Hz Input
Code
Amps
Hp
Quantity
Required
Equivalent
Frame Size
E295
295
300
1
8
E355
355
350
1
E395
395
400
1
E435
435
450
1
E460
460
500
1
E510
510
500
1
E295
595
600
2
9
E355
630
700
2
E395
760
800
2
E435
825
900
2
E460
900
950
2
E510
980
1000
2
E395
1110
1100
3
10
E510
1430
1400
3
To achieve the extended ratings listed for Frames 9 and 10, the base
Frame 8 drive must be paralleled 2 or 3 times. Refer to the Drive
Rating tables on pages 8, 9, 12, and 13 for detailed information.
f4
ND Rating
690V AC / 932V DC, 60 Hz Input (not UL listed)
Code
Amps
kW
Quantity
Required
Equivalent
Frame Size
F265
265
250
1
8
F330
330
315
1
F370
370
355
1
F415
415
400
1
F460
460
450
1
F500
500
500
1
F265
590
560
2
9
F330
650
630
2
F370
710
710
2
F415
765
750
2
F460
795
800
2
F500
960
900
2
F370
1040
1000
3
10
F500
1400
1400
3
To achieve the extended ratings listed for Frames 9 and 10, the base
Frame 8 drive must be paralleled 2 or 3 times. Refer to the Drive
Rating tables on pages 8, 9, 12, and 13 for detailed information.
g
Filtering and CM Cap Configuration
‡
Code
Filtering
Default CM Cap Connection
A
Yes
Jumper Removed
J
Yes
Jumper Installed
‡
480V drives must select code "A." Jumpers are included for field
reconfiguration as desired.
h
Dynamic Braking
§
Code
Internal Resistor
Internal Transistor
N
No
No
§
Not available on Frames 8…10.