beautypg.com

N in, Figure 5, Enclosure fans – Rockwell Automation 20G PowerFlex 755 IP00 NEMA/UL Open Drive - Frames 8-10 User Manual

Page 20: O static pressure

background image

20

Rockwell Automation Publication 750-IN020C-EN-P - May 2012

PowerFlex 755 IP00, NEMA/UL Open Type Drive

Enclosure Fans

Enclosure fans are required and must meet or exceed the performance shown in

Figure 5

for two fans operating at 10.76 CMM (380 CFM) each with 1.27 mm

(0.05 in.) H

2

O static pressure.

Figure 5 - Fan Performance (per bay)

The enclosure fans can be powered from the Control Transformer which is
located in the upper part of the drive assembly. The transformer supplies 230V
AC (±10%) power to the drive and drive blower with sufficient power available
(240 VA/bay) for the enclosure fans. The terminating point for the enclosure fans
is at terminal block TB2 on the right side of the drive assembly (see

Figure 6

).

Recommended wire is 1.3 mm

2

(16 AWG) tinned copper stranded

conductor, PVC insulated, 600V, 105 °C.

Recommended Connector; Phoenix P/N 1757019, 5.08 mm pitch, 2
position, 12A, 250V, 24…12 AWG.

To gain access to the Control Transformer, refer to the PowerFlex 750-Series
Hardware Service Manual, publication 750-TG001. To select or verify
transformer primary voltage, refer to

page 41

.

For Common DC Input drives, the user must provide:

1.

Electrical power to the drive for the enclosure fans, and

2.

overload protection for the drive control transformer. The overload device
must be suitable for 120/240V AC, 50/60 Hz, 8.3/4.2 A, 1 kVA.

Allen-Bradley circuit breaker catalog number 1489-A2D130 is acceptable.
A circuit breaker lock (1489-AALOA) is also available.

For additional information, refer to the PowerFlex 750-Series Installation
Instructions, publication 750-IN001. See the section “120V/240V AC Power
Supply Connections - Common DC Input Drives.”

0.00

25.0

20.0

15.0

10.0

5.0

0.00

0.98

0.78

0.59

0.39

0.20

0.00

2.55

5.09

7.64

10.19

12.75

0.00

90.0

180.0

270.0

360.0

450.0

Flowrate (CMM)

Flowrate (CFM)

Sta

tic P

ressur

e (mmA

q)

Sta

tic P

ressur

e (InA

q)

50 Hz

60 Hz

Typical enclosure pressure with
ventilation requirements described in

Figure 1