Power terminals – Rockwell Automation 20G PowerFlex 755 IP00 NEMA/UL Open Drive - Frames 8-10 User Manual
Page 47

Rockwell Automation Publication 750-IN020C-EN-P - May 2012
47
PowerFlex 755 IP00, NEMA/UL Open Type Drive
Power Terminals
For easier power wiring, movable L-bracket assemblies are included with the
Field Termination kits to connect the AC line input, output to the motor, and
DC bus power. Arrange the moveable L-brackets and secure using the torque
guidelines listed. Refer to pages
for kit installation guidelines and
for recommended mounting locations and dimensions.
ATTENTION: To guard against drive damage, Do Not connect power wires
directly to the drive power terminals. Power wiring must be connected to bus
bars which are fastened to the drive power terminals. Refer to
W/T3
V/T2
U/T1
-DC
+DC
T/L3
S/L2
R/L1
TESTPOINTS
DC-
DC+
TESTPOINTS
DC-
DC+
Inverter/Converter
Assembly Shown
Do Not connect field
wiring directly to power
terminals
Bus Bar to Power
Terminal Detail
M10 x 35 mm SEMS
Torque: 22.4 N•m
(200 lb•in)