For a list of non – Rockwell Automation 440R Guardmaster EtherNet/IP Network Interface User Manual User Manual
Page 56
56
Rockwell Automation Publication 440R-UM009B-EN-P - February 2014
Appendix D
Tag Definitions
Table 10 - GSR EM(D) NonRecoverableFault_A and NonRecoverableFault_B Fault Codes
Fault
Code
Description
Corrective Action
00H
No fault
None
01H
RAM test fault
Do one of the following:
• Power cycle the safety relay.
• Reconfigure the safety relay.
• Validate the electrical installation and appropriate
measures to reduce noise and suppress surges are taken.
02H
Stack over-/under-flow
03H
Configuration mismatch between
Processors A and B
04H
Internal timing fault
05H
EEPROM read/write failure
06H
B1 configuration fault
Do one of the following:
• Check the wiring to terminal B1.
• Reconfigure the safety relay.
• Validate the electrical installation and appropriate
measures to reduce noise and suppress surges are taken.
07H
Mismatch between current switch
settings (switch 1: Range) and setting
stored during power-up.
Do one of the following:
• Change the switch settings to the correct values.
• Power cycle the safety relay.
• Reconfigure the safety relay.
technical support representative. For contact information, see:
08H
Mismatch between current switch
settings (switch 2: Time) and setting
stored during power-up.
09H
SPI compare fault
Do one of the following:
• Power cycle the safety relay.
• Reconfigure the safety relay.
• Validate the electrical installation and appropriate
measures to reduce noise and suppress surges are taken.
0BH
ROM test failure
11H
Pulse test fault on main transistor
Do one of the following:
• Check wiring for shorts to 24V or other channels.
• Power cycle the safety relay.
• Reconfigure the safety relay.
• Validate the electrical installation and appropriate
measures to reduce noise and suppress surges are taken.
12H
Pulse test fault of transistor for safety
output channel 1
13H
Pulse test fault of transistor for safety
output channel 2