Rockwell Automation 440R Guardmaster EtherNet/IP Network Interface User Manual User Manual
Page 53
![background image](/manuals/578097/53/background.png)
Rockwell Automation Publication 440R-UM009B-EN-P - February 2014
53
Tag Definitions
Appendix D
06H
Safety mat wiring detected on one of
the input pairs while the safety relay is
configured for ‘OR’ logic
Do one of the following:
• If there are no safety mats, check the input wiring (safety
mat wiring is crossed from normal dual-channel device
wiring)
• Change the safety relay to ‘AND’ logic.
technical support representative. For contact information, see:
07H
Mismatch between current switch
settings and setting stored during
power-up
Do one of the following:
• Change the switch settings to the correct values.
• Power cycle the safety relay.
• Reconfigure the safety relay.
technical support representative. For contact information, see:
09H
SPI compare fault
Do one of the following:
• Power cycle the safety relay.
• Reconfigure the safety relay.
• Validate the electrical installation and appropriate
measures to reduce noise and suppress surges are taken.
0BH
ROM test failure
0CH
Terminal S12 hardware input fault
0DH
Terminal S22 hardware input fault
0EH
Terminal S32 hardware input fault
0FH
Terminal S42 hardware input fault
10H
Terminal S34 hardware input fault
11H
Pulse test fault on main transistor
Do one of the following:
• Check wiring for shorts to 24V or other channels.
• Power cycle the safety relay.
• Reconfigure the safety relay.
• Validate the electrical installation and appropriate
measures to reduce noise and suppress surges are taken.
12H
Pulse test fault of transistor for safety
output channel 1
13H
Pulse test fault of transistor for safety
output channel 2
14H-1EH
Internal plausibility test fault
Do one of the following:
• Power cycle the safety relay.
• Reconfigure the safety relay.
• Validate the electrical installation and appropriate
measures to reduce noise and suppress surges are taken.
If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:
1FH
Different Single Wire Safety input signal
detected at Processor A than Processor B
20H, 21H
Internal program fault
22H, 23H
Rotary switch read error
24H
Cross fault at processor pins for safety
outputs
25H
Under voltage detected
Do one of the following:
• Validate the electrical installation and appropriate supply
voltage is provided.
• Power cycle the safety relay.
• Reconfigure the safety relay.
If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:
26H
Fault detected in the other Processor
If viewing the NonrecoverableFault_A tag, refer to
NonrecoverableFault_B tag.
If viewing NonrecoverableFault_B tag refer to
NonrecoverableFault_A tag.
Table 7 - GSR DI(S) NonRecoverableFault_A and NonRecoverableFault_B Fault Codes
Fault
Code
Description
Corrective Action