Chapter 5
Troubleshoot the Interface
Table 2 - Status Indicators for 440R-ENETR Interface
Status
Description
Module status
Off
No power applied to device
Solid green
Device operating normally
Flashing green
Device needs commissioning due to missing, incomplete, or incorrect configuration.
Flashing red/green
Module self-test
Flashing red
Recoverable fault.
Complete firmware update, verify address switches. Check for monitored safety relay fault.
Solid red
Unrecoverable fault, may require device replacement.
Network status
Off
Device is not online
- Device has not completed Dup_MAC_ID test.
- Device not powered - check module status indicator.
Flashing green
Device is online but has no CIP connections in the established state.
Solid green
Device online and has CIP connections in the established state.
Flashing red
One or more CIP connections in timed-out state.
Check for Guardmaster safety relay failure and controller operation.
Solid red
Duplicate IP address detected.
Verify IP address setting and correct, as needed.
Link 1 or Link 2 Activity / Status
Off
No link established.
Solid green
One of the following conditions exist:
• A 100 Mbps (full or half duplex) link exists.
• The ring network is operating normally.
Flashing green
Transmit or receive activity present on indicated port @ 100 Mbps.
Solid yellow
One of the following conditions exist:
• A 10 Mbps (full or half duplex) link exists.
• The ring network is operating normally.
Flashing yellow
Transmit or receive activity present on indicated port @ 10 Mbps.