Rockwell Automation 440R Guardmaster EtherNet/IP Network Interface User Manual User Manual
Page 52
![background image](/manuals/578097/52/background.png)
52
Rockwell Automation Publication 440R-UM009B-EN-P - February 2014
Appendix D
Tag Definitions
Slotx_GSR_DIS_S42
BOOL
S42 Status – Indicates whether terminal S42 of circuit IN02
is On or Off.
0 = The terminal is Off.
1 = The terminal is On.
Slotx_GSR_DIS_L12
BOOL
L12 Status – Indicates whether terminal L12 is On or Off.
0 = The terminal is Off.
1 = The terminal is On.
Slotx_GSR_DIS_S34
BOOL
S34 Status – Indicates whether terminal S34 is On or Off.
0 = The terminal is Off.
1 = The terminal is On.
Slotx_GSR_DIS_NonRecoverableFault_A
SINT
Non-Recoverable Fault Processor A – Indicates a
nonrecoverable fault has been recorded by Safety Processor
A. See
for a list of non-recoverable fault
codes.
Slotx_GSR_DIS_NonRecoverableFault_B
SINT
Non-Recoverable Fault Processor B – Indicates a
nonrecoverable fault has been recorded by Safety Processor
B. See
for a list of non-recoverable fault
codes.
Slotx_GSR_DIS_S12OpenWire
BOOL
S12 Open Wire - Indicates S12 open (0) and closed (1)
while S22 remained closed (1).
Slotx_GSR_DIS_S22OpenWire
BOOL
S22 Open Wire - Indicates S22 open (0) and closed (1)
while S12 remained closed (1).
Slotx_GSR_DIS_S32OpenWire
BOOL
S32 Open Wire - Indicates S32 open (0) and closed (1)
while S42 remained closed (1).
Slotx_GSR_DIS_S42OpenWire
BOOL
S42 Open Wire - Indicates S42 open (0) and closed (1)
while S32 remained closed (1).
Slotx_GSR_DIS_CrossLoopFault
BOOL
Cross Loop Fault – Indicates whether the safety relay has
detected a cross loop fault on one of the input circuits.
0 = No fault
1 = Cross loop fault
Slotx_GSR_DIS_InvalidSwitchSetting
BOOL
Invalid Switch Settings – Indicates the switch settings
changed after power-up of the safety relay.
0 = No fault
1 = Fault
Slotx_GSR_DIS_ResetHeldOn
BOOL
Reset Held On Fault – Indicates the reset signal On (1) for
longer than the maximum time of 3000 ms.
0 = No fault
1 = Fault
Table 7 - GSR DI(S) NonRecoverableFault_A and NonRecoverableFault_B Fault Codes
Fault
Code
Description
Corrective Action
00H
No fault
None
01H
RAM test fault
Do one of the following:
• Power cycle the safety relay.
• Reconfigure the safety relay.
• Validate the electrical installation and appropriate
measures to reduce noise and suppress surges are taken.
02H
Stack over-/under-flow
03H
Configuration mismatch between
Processors A and B
04H
Internal timing fault
05H
EEPROM read/write failure
Table 6 - GSR DI(S) Module Input Tags
Name
Data Type
Definition