Viewing the option module status using parameters, Updating the option module firmware – Rockwell Automation 20-750-PNET2P Profinet Dual Port Option Module User Manual
Page 40
40
Rockwell Automation Publication 750COM-UM007A-EN-P - January 2013
Chapter 3 Configuring the Option Module
9.
Reset the option module using
Device Parameter 05 - [Reset Module] or
by cycling power to the drive so that the restored parameters take effect.
Viewing the Option Module
Status Using Parameters
The following parameters provide information about the status of the option
module. You can view these parameters at any time.
Updating the Option
Module Firmware
The option module firmware can be updated over the network through a direct
connection from a computer to only the 20-750-PNET2P option module Port 1
connector. You can use the Allen-Bradley ControlFLASH software tool, the
built-in update capability of DriveExplorer Lite or Full software, or the built-in
update capability of DriveExecutive software.
To obtain a firmware update for this option module, go to
. This website contains all firmware update files and
associated Release Notes that describe the following items:
• Firmware update enhancements and anomalies
• How to determine the existing firmware revision
• How to update the firmware using DriveExplorer, DriveExecutive, or
ControlFLASH software
Option Module
Device Parameter
Description
02 - [DLs From Net Act]
The number of controller-to-drive Datalinks that are included in the
network I/O connection (controller outputs).
03 - [DLs To Net Act]
The number of drive-to-controller Datalinks that are included in the
network I/O connection (controller inputs).
04 - [Net Addr Src]
Displays the source from which the option module network address is
taken. It is either the values of configured option module parameters
or from DCP-DHCP.
IMPORTANT
To update the option module, the IP Address Selection Jumper must be
connected across pins 2 and 3. This can be easily verified by viewing the
value of read-only Device Parameter 04 - [Net Addr Src], which must
be ‘1’ (Config). If the value is ‘0’ (DCP-DHCP), you must change the IP
Address Selection Jumper from being across pins 1 and 2 to being across
pins 2 and 3.