Configuring the Option Module Chapter 3
Setting Web Page Access
By using a web browser to access the IP address set for the option module, you can
view the option module web pages for information about the module, the drive,
and other DPI devices connected to the drive, such as HIMs or converters.
By default, the option module web pages are disabled. To enable the option
module web pages, set
Device Parameter 19 - [Web Enable] to ‘1’ (Enabled) and
then reset the option module for the change to take effect.
For more details on the option module web pages, see
.
The option module can be configured to automatically send e-mail messages to
desired addresses when selected drive faults occur and/or are cleared, and/or
when the option module takes a communication or idle fault action.
Bit 0 of
Device Parameter 20 - [Web Features] is used to protect the configured
settings for e-mail messaging. By default, settings are not protected and the user
can make changes. To protect the configured settings, set the value of E-mail Cfg
Bit 0 to ‘0’ (Disabled). You can unprotect the configuration by changing Bit 0
back to ‘1’ (Enabled). E-mail messaging will always remain active regardless of
whether or not its settings are protected—unless e-mail messaging was never
configured. For more information about configuring option module e-mail
messaging or to stop e-mail messages, see
Configure E-mail Notification Web
Bit 0 is the right most bit. In the example above, it equals ‘1’ (Enabled).
Changes to this parameter take effect immediately. A reset is not required.
Value
Setting
0
Disabled (Default)
1
Enabled
ESC
ENTER
Stopped
0.00 Hz
AUTO
▲
▼
Edit Web Enable
Disabled
0
0 << 1
Bit
Description
0
E-mail Cfg (Default = 1 = Enabled)
1...7
Not Used
ESC
ENTER
Stopped
0.00 Hz
AUTO
▲
▼
Edit Web Features
xxxx xxx1
E-mail Cfg