Configuring the Option Module Chapter 3
Using DHCP
The option module can be configured to use a DHCP server to establish the IP
address settings for the module.
1.
Verify that IP Address Selection Jumper is on Pins 1 and 2 and the value of
Device Parameter 04 - [Net Addr Src] is ‘0’ (DCP-DHCP).
2.
Set the value of
Device Parameter 18 - [DHCP] to ‘1’ (Enabled) to select
the DHCP server as the source for the IP address.
3.
Reset the option module; see
Resetting the Option Module on page 38
Using Option Module Parameters
If the IP Address Selection Jumper is on Pins 2 and 3, the network address can be
configured using option module parameters or the default network address
which is:
• IP Address 192.168.0.1
• Subnet Mask 255.255.255.0
• Gateway Address 192.168.0.1
Set the IP Address
1.
Verify that IP Address Selection Jumper is on Pins 2 and 3 and the value of
Device Parameter 04 - [Net Addr Src] is ‘1’ (Config).
2.
Set the value of
Device Parameters 06 - [IP Addr Cfg 1] through 09 - [IP
Addr Cfg 4]
to a unique IP address.
3.
Reset the option module; see
Resetting the Option Module on page 38
Set the Subnet Mask
1.
Verify that IP Address Selection Jumper is on Pins 2 and 3 and the value of
Device Parameter 04 - [Net Addr Src] is ‘1’ (Config).
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
Edit IP Addr Cfg 1
0
0 << 255
Default = 0.0.0.0
255.255.255.255
[IP Addr Cfg 1]
[IP Addr Cfg 2]
[IP Addr Cfg 3]
[IP Addr Cfg 4]