Rockwell Automation Publication 750COM-UM007A-EN-P - January 2013

31

Configuring the Option Module Chapter 3

Using DHCP

The option module can be configured to use a DHCP server to establish the IP
address settings for the module.

1.

Verify that IP Address Selection Jumper is on Pins 1 and 2 and the value of

Device Parameter 04 - [Net Addr Src] is ‘0’ (DCP-DHCP).

2.

Set the value of

Device Parameter 18 - [DHCP] to ‘1’ (Enabled) to select

the DHCP server as the source for the IP address.

3.

Reset the option module; see

Resetting the Option Module on page 38

.

Using Option Module Parameters

If the IP Address Selection Jumper is on Pins 2 and 3, the network address can be
configured using option module parameters or the default network address
which is:

• IP Address 192.168.0.1
• Subnet Mask 255.255.255.0
• Gateway Address 192.168.0.1

Set the IP Address

1.

Verify that IP Address Selection Jumper is on Pins 2 and 3 and the value of

Device Parameter 04 - [Net Addr Src] is ‘1’ (Config).

2.

Set the value of

Device Parameters 06 - [IP Addr Cfg 1] through 09 - [IP

Addr Cfg 4]

to a unique IP address.

3.

Reset the option module; see

Resetting the Option Module on page 38

.

Set the Subnet Mask

1.

Verify that IP Address Selection Jumper is on Pins 2 and 3 and the value of

Device Parameter 04 - [Net Addr Src] is ‘1’ (Config).