Rockwell Automation 22B PowerFlex 40 Configured AC Drives User Manual
Page 56

56
Rockwell Automation Publication 23B-IN001K-EN-P - September 2013
Appendix A
Specifications
Dynamic Braking
Internal brake IGBT included with all ratings
Environment
Altitude:
1000 m (3300 ft) max. without derating
Storage Temperature:
–40 to 85 degrees C (–40 to 185 degrees F)
Atmosphere:
Important: Drive must not be installed in an area where the ambient atmosphere contains volatile or
corrosive gas, vapors or dust. If the drive is not going to be installed for a period of time, it must be stored in an
area where it will not be exposed to a corrosive atmosphere.
Relative Humidity:
0 to 95% non-condensing
Shock (operating):
15G peak for 11ms duration (±1.0ms)
Vibration (operating):
1G peak, 5 to 2000 Hz
Control
Frequency Accuracy
Digital Input:
Within ±0.05% of set output frequency.
Analog Input:
Within 0.5% of maximum output frequency.
Analog Output:
±2% of full scale, 10-bit resolution.
Speed Regulation - Open Loop with Slip Compensation:
±2% of base speed across a 40:1 speed range.
1% of base speed across a 60:1 speed range.
Stop Modes:
Multiple programmable stop modes including - Ramp, Coast, DC-Brake, Ramp-to-Hold and S Curve.
Accel/Decel:
Two independently programmable accel and decel times. Each time may be programmed from 0…600
seconds in 0.1 second increments.
Intermittent Overload:
150% Overload capability for up to 1 minute; 200% Overload capability for up to 3 seconds.
Electronic Motor Overload Protection: Class 10 motor overload protection according to NEC article 430 and motor over-temperature protection
according to NEC article 430.126 (A)(2). UL File E59272.