Rockwell Automation 22B PowerFlex 40 Configured AC Drives User Manual
Page 25

Rockwell Automation Publication 23B-IN001K-EN-P - September 2013
25
PowerFlex 40 Standard Configured Drive Standard Features and Options
Chapter 1
DeviceNet Point I/O w/IB4 (4 Inputs) (Position 16+, Code R4)
This option provides a factory installed 1734-ADNX Point I/O Scanner in
combination with a 1734-IB4 (4 input) four point, 24V DC sink input.
The drive DeviceNet is prewired to the subnet connector of the 1734-ADNX.
The customer is required to make the DeviceNet connection directly to the
1734-ADNX network connector. The 1734-IB4 is connected via a backplane
offering four available inputs for customer use.
The Point I/O Scanner allows data to be gathered from the drive mounted
DeviceNet and the 1734-IB4 (4 input) appear as one node on the
communication system.
Refer to publication 1734-IN051 for more detail on the 1734-IB4.
Component Specifications
This option must be used with the drive mounted DeviceNet option D (Position
12) and is not compatible with options 4, C, E, P (Position 12), R3, or R5.
Note: Customer is required to supply external 24V DC/AC to power 1734-
ADNX scanner.
1734-ADNX Devices
IEC style, Internationally rated
Meet IP65/IP66 and NEMA/UL Type 4/4X/13
UL Listed, CSA Certified
10 amp contacts
Screw terminals, 0.3…3.5 mm
2
(22…12 AWG) maximum
1734-IB4 Devices
Refer to publication 1734-IN051
Schematic