The following tables provide specifications for the PowerFlex 40 configured AC
drives.
Specifications Tables
Table 6 - Standard Configured Drive Products
Table 7 - Standard PowerFlex 40 Drives
Input/Output Ratings
Output Frequency: 0…400
Hz
(Programmable)
Efficiency: 97.5%
(Typical)
Approvals
Fuses and Power
Disconnecting Means
140M Motor Circuit Protector:
Provides branch circuit protection, see
for short circuit withstand rating, on grounded wye
neutral distribution systems only
194R Fused Disconnect:
Provides branch circuit protection, 200 kA short circuit withstand, Class J fuses
Protective Features
Over Voltage:
480V AC Input – Trip occurs at 810V DC bus voltage (equivalent to 575V AC incoming line)
Under Voltage:
480V AC Input – Trip occurs at 390V DC bus voltage (equivalent to 275V AC incoming line)
Environment
Ambient Operating Temperature, NEMA 4/12, 4X (IP66): –10 to 40 degrees C (14 to 104 degrees F)
(1)
Cooling Method:
Fan (All drive ratings)
Control
Carrier Frequency:
2…4 kHz. Drive rating and heat calculations are based on 4 kHz.
(1) The design of the PowerFlex 40 Standard Configured Drive NEMA 4/12 and 4X packages support indoor and outdoor applications that are not in direct sunlight. When optional Door Mounted HIM is
supplied, enclosure is rated for indoor use only.
UL
®
LIS
TED 966X
IND C
O NT EQ
UL508C
UL
®
LIS
TED 966X
IND C
O NT EQ
C
CSA C 22.2 No. 14
Digital Control Inputs
(Input Current = 6 mA)
SRC (Source) Mode:
18…24 Volts = ON; 0…6 Volts = OFF
SNK (Sink) Mode:
0…6 Volts = ON; 18…24 Volts = OFF
Analog Control Inputs
4-20mA Analog:
250 ohm input impedance
0-10V DC Analog:
100k ohm input impedance
External Pot:
1…10k ohms, 2 Watt minimum
Control Output
Programmable Output (form C relay)
Resistive Rating:
3.0A at 30V DC, 3.0A at 125V AC, 3.0A at 240V AC
Inductive Rating:
0.5A at 30V DC, 0.5A at 125V AC, 0.5A at 240V AC
Opto Outputs
30V DC, 50 mA
Non-inductive
Analog Output (10-bit)
0-10V, 1k ohm Min.
Fuses and Circuit Breakers
Recommended Fuse Type:
UL Class J, CC, T or Type BS88; 600V (550V) or equivalent.
Recommended Circuit Breakers: HMCP circuit breaker or equivalent.
Protective Features
Motor Protection:
I
2
t overload protection – 150% for 60 Secs, 200% for 3 Secs (Provides Class 10 protection)
Overcurrent:
200% hardware limit, 300% instantaneous fault
Control Ride Through:
Minimum ride through is 0.5 Secs - typical value 2 Secs
Faultless Power Ride Through: 100
milliseconds