Rockwell Automation 22B PowerFlex 40 Configured AC Drives User Manual
Page 14
![background image](/manuals/577167/14/background.png)
14
Rockwell Automation Publication 23B-IN001K-EN-P - September 2013
Chapter 1
PowerFlex 40 Standard Configured Drive Standard Features and Options
Main Fuses (F1-F3)
Input line branch circuit protection fuses must be used to protect the input
power lines. If input fuses are not provided with your drive, recommended fuse
values are shown in
Table 2
. The input fuse ratings listed in
Table 2
are applicable
for one drive per branch circuit. No other load may be applied to that fused
circuit.
The recommended fuse type for all PowerFlex 40 Standard Configured Drives is
UL Class J.
Table 2 - Branch Fusing
ATTENTION: Most codes require that upstream branch circuit protection be
provided to protect input power wiring. Install the fuses recommended in
Table
2
. Do not exceed the fuse ratings. Failure to observe this precaution could result
in damage to, or destruction of, the equipment.
Voltage Rating
Drive Rating HP
Fuse Rating Amps
480V AC
0.5
3
1.0
6
2.0
10
3.0
15
5.0
20
7.5
25
10
30
15
50