Chapter 1
PowerFlex 40 Standard Configured Drive Standard Features and Options
Auto/Manual Selector Switch (Position 16+, Code S4)
This 800F door mounted operator device is factory installed and provides an
Auto/Manual selector switch.
The Auto/Manual selector switch determines the source of the actual drive speed
reference. Using 2-wire control in Auto mode, speed source is parameter A071
[Preset Freq 1]. In Manual mode, the speed source is parameter A072 [Preset
Freq 2].
If the door mounted speed potentiometer (Option S18) is supplied and it is
intended to be the speed reference in Manual mode, set parameter P052 [Digital
In2 Sel] to option 13 “10V In Ctrl.” Refer to the table below and the PowerFlex
40 User Manual, publicatio
Auto/Manual Selector Switch (Code S4)
Component Specifications
This option is not compatible with Codes R3, R5, S1, S20, S21 or S22.
Speed Reference
Parameter Settings
Manual Mode
Auto Mode
P038 [Speed Reference]
A051 [Digital In1 Sel]
A052 [Digital In2 Sel]
Preset Speed
Preset Speed
4 “Preset Freq”
4 “Preset Freq”
4 “Preset Freq”
Analog Input (0-10V)
4 “Preset Freq”
13 “10V In Ctrl”
4 “Preset Freq”
Analog Input (4-20mA)
4 “Preset Freq”
14 “20mA In Ctrl”
4 “Preset Freq”
Communication Port
(1)
4 “Preset Freq”
6 “Comm Port”
4 “Preset Freq”
Speed Pot (Door)
Preset Speed
4 “Preset Freq”
4 “Preset Freq”
13 “10V In Ctrl”
Analog Input (4-20mA)
4 “Preset Freq”
14 “20mA In Ctrl”
13 “10V In Ctrl”
Communication Port
(1)
4 “Preset Freq”
6 “Comm Port”
13 “10V In Ctrl”
HIM (Door)
Preset Speed
4 “Preset Freq”
4 “Preset Freq”
6 “Comm Port”
Analog Input (0-10V)
4 “Preset Freq”
13 “10V In Ctrl”
6 “Comm Port”
Analog Input (4-20mA)
4 “Preset Freq”
14 “20mA In Ctrl”
6 “Comm Port”
(1) Communication port will have both logic and reference control.
Bulletin 800F Devices
IEC style, Internationally rated
Meet IP65/IP66 and NEMA/UL Type 4/4X/13
UL Listed, CSA Certified
10 amp contacts
Screw terminals, 0.3…3.5 mm
2
(22…12 AWG) maximum
Auto/Manual
Selector Switch
2 position, Maintained
1 N.C. contact
Legend Plate
30 x 50 mm, Black with white lettering
Wiring
0.8 mm
2
(18 AWG), Blue
Schematics