Rockwell Automation 20-COMM-P Profibus Adapter User Manual
Page 99

Adapter Parameters
B-3
11
[DPI I/O Config]
I/O that is transferred through the adapter.
Default:
xxx0 0001
Bit Values:
0 = I/O disabled
1 = I/O enabled
Type:
Read/Write
Reset Required:
Yes
Bit Definitions
0 = Cmd/Ref
1 = Datalink A
2 = Datalink B
3 = Datalink C
4 = Datalink D
5 = Not Used
6 = Not Used
7 = Not Used
12
[DPI I/O Active]
I/O that the adapter is actively transmitting. The
value of this parameter will usually be equal to the
value of Parameter 11- DPI I/O Config.
Default:
xxx0 0001
Bit Values:
0 = I/O disabled
1 = I/O enabled
Type:
Read Only
Bit Definitions
0 = Cmd/Ref
1 = Datalink A
2 = Datalink B
3 = Datalink C
4 = Datalink D
5 = Not Used
6 = Not Used
7 = Not Used
13
[Flt Cfg Logic]
Sets the Logic Command data that is sent to the
drive if any of the following is true:
• Parameter 09 - [Comm Flt Action] is set to
Send Flt Cfg and communications are
disrupted.
• Parameter 10 - [Idle Fault Action] is set to
Send Flt Cfg and the scanner is put into
Program mode.
The bit definitions will depend on the product to
which the adapter is connected.
Default:
0000 0000 0000 0000
Minimum:
0000 0000 0000 0000
Maximum:
1111 1111 1111 1111
Type:
Read/Write
Reset Required:
No
14
[Flt Cfg Ref]
Sets the Reference data that is sent to the drive if
any of the following is true:
• Parameter 09- [Comm Flt Action] is set to
Send Flt Cfg and communications are
disrupted.
• Parameter 10 - [Idle Flt Action] is set to Send
Flt Cfg and the scanner is put into Program
mode.
Default:
0
Minimum:
0
Maximum:
4294967295
Type:
Read/Write
Reset Required:
No
Important: If the drive uses a 16-bit
Reference, the most significant word of this
value must be set to zero (0) or a fault will
occur.
Parameter
No. Name and Description
Details
Bit
Default
1
0
0
0
0
x x
x
0
1
2
3
4
5
7 6
Bit
Default
1
0
0
0
0
x x
x
0
1
2
3
4
5
7 6