Port status indicator, Port status indicator -2 – Rockwell Automation 20-COMM-P Profibus Adapter User Manual
Page 88
![background image](/manuals/576951/88/background.png)
7-2
Troubleshooting
ti
PORT Status Indicator
Status
Cause
Corrective Action
Off
The adapter is not powered
or is not connected
properly to the drive.
• Securely connect the adapter to the drive
using the ribbon cable.
• Apply power to the drive.
Flashing Red
The adapter is not
receiving a ping message
from the drive.
• Verify that cables are securely connected.
• Cycle power to the drive.
Solid
Red
The drive has refused an
I/O connection from the
adapter.
Another DPI peripheral is
using the same DPI port as
the adapter.
Important: Cycle power to the product after
making any of the following corrections.
• Verify that all DPI cables on the PowerFlex
drive are securely connected and not
damaged. Replace cables if necessary.
• Verify that the PowerFlex drive supports
Datalinks.
• Configure the adapter and PowerFlex drive
to use a Datalink that is not already being
used by another peripheral.
Orange
The adapter is connected
to a product that does not
support Allen-Bradley DPI
communications.
• Connect the adapter to a product that
supports Allen-Bradley DPI communications
(for example, PowerFlex drives).
Flashing Green
The adapter is establishing
an I/O connection to the
drive.
• No Action. This status indicator will turn solid
green or red.
Solid Green
The adapter is properly
connected and is
communicating with the
drive.
• No Action.