Adapter diagnostic items, Adapter diagnostic items -4 – Rockwell Automation 20-COMM-P Profibus Adapter User Manual
Page 90
![background image](/manuals/576951/90/background.png)
7-4
Troubleshooting
Adapter Diagnostic Items are viewable with DriveExplorer (version 2.01
or higher), DriveExecutive (version 1.01 or higher) or HIM (2.001)
software.
Adapter Diagnostic Items
No.
Event
Description
1
Common Logic
Cmd
The current value of the Common Logic Command being transmitted
to the host.
2
Prod Logic Cmd
The current value of the Product-specific Logic Command being
transmitted to the host.
3
Reference
The current value of the Product-specific Reference being
transmitted to the host.
4
Common Logic
Sts
The current value of the Common Logic Status being received from
the host.
5
Prod Logic Sts
The current value of the Product-Specific Status being received from
the host.
6
Feedback
The current value of the Product-Specific Feedback being received
from the host.
7
Datalink A1 In
The current value of Datalink A1 being transmitted to the host.
(Value of 0 if datalink is not used).
8
Datalink A2 In
The current value of Datalink A2 being transmitted to the host.
(Value of 0 if datalink is not used).
9
Datalink B1 In
The current value of Datalink B1 being transmitted to the host.
(Value of 0 if Datalink is not used).
10
Datalink B2 In
The current value of Datalink B2 being transmitted to the host.
(Value of 0 if Datalink is not used).
11
Datalink C1 In
The current value of Datalink C1 being transmitted to the host.
(Value of 0 if Datalink not used).
12
Datalink C2 In
The current value of Datalink C2 being transmitted to the host.
(Value of 0 if Datalink is not used).
13
Datalink D1 In
The current value of Datalink D1 being transmitted to the host.
(Value of 0 if Datalink is not used).
14
Datalink D2 In
The current value of Datalink D2 being transmitted to the host.
(Value of 0 if Datalink is not used).
15
Datalink A1 Out
The current value of Datalink A1 being received from the host.
16
Datalink A2 Out
The current value of Datalink A2 being received from the host.
17
Datalink B1 Out
The current value of Datalink B1 being received from the host.
18
Datalink B2 Out
The current value of Datalink B2 being received from the host.
19
Datalink C1 Out
The current value of Datalink C1 being received from the host.
20
Datalink C2 Out
The current value of Datalink C2 being received from the host.
21
Datalink D1 Out
The current value of Datalink D1 being received from the host.
22
Datalink D2 Out
The current value of Datalink D2 being received from the host.
23
Field Flash Cnt
The number of times this device has been flash updated.
24
DPI Rx Errors
The current value of the DPI CAN Receive error counter.
25
DPI Tx Errors
The current value of the DPI CAN Transmit error counter.
26
PbusImage Siz
Buffer size of Active I/O image (Profibus size) in bytes.
27
Switch 0
The value of Switch 0. (Node Address 1’s digit)
28
Switch 1
The value of Switch 1. (Node Address 10’s digit)
20COMM-UM006A-EN-P.book Page 4 Friday, September 28, 2001 10:43 AM