Connecting the adapter to the network – Rockwell Automation 20-COMM-P Profibus Adapter User Manual
Page 16
2-2
Installing the Adapter
1. Set the node address switches.
Figure 2.1 Setting the Node Address
1. Remove power from the drive.
2. Use static control precautions.
3. Route the PROFIBUS cable through the bottom of the PowerFlex
drive. (See
4. Connect a Profibus connector to the cable. (See
and
.)
[Note: PROFIBUS connectors are available from a variety of sources
and in various sizes. As such, there may be mechanical limitations
that prohibit the use of some connectors. Phoenix Subcon Plus M1
(Part # 2761826) or ERNI Profibus vertical (Node Part # 103658 and
Termination Part # 103659 connectors), are recommended for use
with PowerFlex 70/700 drives.]
Setting
Description
0-99
Node address used by the adapter if switches are enabled. The default
switch setting is 05.
Important: If the address switch is set to “00”, the adapter will use the setting
of Parameter 03 - [P-DP Addr Cfg] for the node address. Refer to
2
1
0
9
8
3
4
5
6
7
2
1
0
9
8
3
4
5
6
7
Tens
Ones
Digit
Digit
Connecting the Adapter to the Network
!
ATTENTION: Risk of injury or death exists. The PowerFlex drive
may contain high voltages that can cause injury or death. Remove
power from the drive, and then verify power has been discharged before
installing or removing an adapter.