Appendix b, Adapter parameters, About parameter numbers – Rockwell Automation 20-COMM-P Profibus Adapter User Manual
Page 97: Parameter list, Appendix b adapter parameters, Adapter, Parameters, Badapter parameters, Appendix
Appendix
B
Adapter Parameters
Appendix B provides information about the PROFIBUS adapter
parameters.
The parameters in the adapter are numbered consecutively. However,
depending on which configuration tool you use, they may have different
numbers.
Topic
Page
About Parameter Numbers
Configuration Tool
Numbering Scheme
• DriveExplorer
• DriveExecutive
• HIM
• Explicit Messaging
The adapter parameters begin with parameter 1. For
example, Parameter 01 - [DPI Port] is parameter 1 as
indicated by this manual.
Parameter List
Parameter
No. Name and Description
Details
01
[DPI Port]
Port to which the adapter is connected. This will
usually be port 5.
Default:
0
Minimum:
0
Maximum:
7
Type:
Read Only
02
[DPI Data Rate]
Data rate used by the drive. This data rate is set in
the drive, and the adapter detects it.
Default:
0 = 125 K
Values:
0 = 125 K
1 = 500 K
Type:
Read Only
03
[P-DP Addr Cfg]
Node address to use if the Node address switches
are set to “00”.
Default:
1
Minimum:
00
Maximum
126
Type:
Read/Write
Reset Required:
Yes
04
[P-DP Addr Actual]
PROFIBUS node address actually used by the
adapter.
Default:
N/A
Minimum:
00
Maximum:
126
Type:
Read Only
20COMM-UM006A-EN-P.book Page 1 Friday, September 28, 2001 10:43 AM