Parameter protocol examples, Slc ladder example - station – Rockwell Automation 20-COMM-P Profibus Adapter User Manual
Page 76
6-6
Using Explicit Messaging (Parameter Protocol)
Parameter Protocol Examples
Read Examples
Figure 6.3 Overview Parameter Message Format (Read Request)
Bit 15-12
11
10-0
15-12
11
10-0
Parameter Access
Word 1 (PCA)
RC
SPM
PNU
RC
SPM
PNU
Parameter Access
Word 2 (IND)
Subindex
Subindex
Parameter Access
Word 3 (PVA)
Not Used
Parameter value high
(32 bit high word)
Parameter Access
Word 4 (PVA)
Not Used
Parameter value low
(32-bit low word/ or
8-bit/16-bit value)
Request
Response
Request
Response
RC
Set to “1” (‘0001’) binary to read
RC
“1” (‘0001’) Transferring 8-bit or 16-bit
parameter value
“2” (‘0010’) Transferring a 32-bit
parameter value
“7” (‘0111’) Request rejected (including fault
code)
SPM
Not used
SPM
Not used
PNU
Parameter number to read
PNU
Confirms the Parameter number (if
successful, equals the PNU from the
request)
Subindex
Selects which DPI port to talk to (“0” = DPI
Host, “5” =20-COMM-P on PowerFlex 70
Subindex
Confirms the DPI port (if successful, equals
the Subindex from the request)
Not Used
Parameter value high word
Contains a “0” if returning a value from a
16-bit parameter and the high word from a
32-bit parameter
Not Used
Parameter value low word
Contains the value from a 8-bit or 16-bit
parameter, the low word if reading from a
32-bit parameter, or the fault code (if RC =
“7”)