Rockwell Automation 20-COMM-P Profibus Adapter User Manual
Page 100
B-4
Adapter Parameters
15
16
17
18
19
20
21
22
[Flt Cfg A1]
[Flt Cfg A2]
[Flt Cfg B1]
[Flt Cfg B2]
[Flt Cfg C1]
[Flt Cfg C2]
[Flt Cfg D1]
[Flt Cfg D2]
Sets the data that is sent to the Datalink in the
drive if any of the following is true:
• Parameter 09 - [Comm Flt Action] is set to
Send Flt Cfg and the scanner is put into
Program mode.
• Parameter 10 - [Idle Flt Action] is set to Send
Flt Cfg and communications are disrupted.
Default:
0
Default:
0
Default:
0
Default:
0
Default:
0
Default:
0
Default:
0
Default:
0
Minimum:
0
Maximum:
4294967295
Type:
Read/Write
Reset Required:
No
Important: If the drive uses 16-bit
Datalinks, the most significant word of this
value must be set to zero (0) or a fault will
occur.
23
[Parameter Mode]
Sets the format used when performing explicit
messages:
• Par Prot (Parameter Protocol) is used to read
or write single parameters.
• DPI Par Prot is reserved for future use.
Performing explicit messaging requires the
“Parameter Access” module to be added when
configuring the node with a network software tool.
Default:
0 = Par Prot
Values:
0 = Par Prot
1 = DPI Par Prot
Type:
Read/Write
Reset Required:
No
24
[P-DP State]
Displays the state of the Profibus controller.
Default:
N/A
Values:
0 = WAIT_PRM
1 = WAIT_CFG
2 = DATA_EX
3 = ERROR
Type:
Read Only
Parameter
No. Name and Description
Details
20COMM-UM006A-EN-P.book Page 4 Friday, September 28, 2001 10:43 AM