Global drive cam loader, Appendix error numbers, causes & remedies – Lenze Global Drive Cam Loader User Manual
Page 51
![background image](/manuals/566345/51/background.png)
L
1.1 EN - 05/2005
51
Global Drive Cam Loader
Appendix
Error numbers, causes & remedies
D401h
Error during the start of the "DriveLC7" com-
ponent.
• Component has not been installed or has
not been registered correctly.
Re-install Cam Loader.
D402h
Error during setting the cam profile data
(points).
Evaluate error description.
D405h
Error during writing the LC7 file.
Check path for the LCx file.
Check if there is enough free space available
on your drive.
Errors within the DriveServer
E7C18000
Error during download preparation.
Repeat download.
E7C18001
PLC has not stopped.
Stop the PLC program in the target system.
E7C18002
Controller inhibit has not been set.
Set controller inhibit in the target system
(e.g. via terminal 28 or code C0040).
E7C18003
Incorrect data type (no LC9 file).
Create new LC9 file.
E7C18004
Check sum test is negative (faulty check
sum).
Repeat download.
Increase time-out time in the system bus
configuration tool (e.g. to 3 seconds).
E7C18005
Item can momentarily not be accessed due to
download.
Repeat download after a few minutes or re-
start your PC.
E7C18006
Target system is momentarily busy copying
RAM blocks.
Start the PLC program in the target system.
E7C18007
Error occurred after the download.
Repeat download.
E7C18008
Error after version comparison during down-
load of an LC7 file.
• Different versions in LC7 file and target
system.
Update the operating system of the 9300 EK.
E7C18009
No template "Cam" in the target system.
Create DDS project based on Template Cam
and transfer it into the target system.
Error number
Cause
Remedy