C13862 | bus counter, C13864 | active station name, C13864 – Lenze E84DxxxxxxxxxR User Manual
Page 72: Communication manual 8400 protec profinet
Communication manual 8400 protec PROFINET
Parameter reference
Parameters relevant for communication
72
L
EDS84DPNET EN 4.0 - 11/2010
C13862
C13864
Parameter | Name:
C13862 | Bus counter
Data type: UNSIGNED_32
Index: 10713
d
= 29D9
h
Display of data cycles per second (irrespective of data changes)
Display range
(min. value | unit | max. value)
0
4294967295
Subcodes
Information
C13862/1
Data cycles per second
C13862/2
Read cycles per second
C13862/3
Write cycles per second
;
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13864 | Active station name
Data type: VISIBLE_STRING
Index: 10711
d
= 29D7
h
Displays the active station name used by the controller.
It may differ from the contents of code
, depending on whether the station name has been changed via the
fieldbus or via
.
Setting the station name ( 25)
Subcodes
Information
C13864/1
1st ... 30th character
C13864/2
31st ... 60th character
C13864/3
61st ... 90th character
C13864/4
91st ... 120th character
C13864/5
121st ... 150th character
C13864/6
151st ... 180th character
C13864/7
181st ... 210th character
C13864/8
211th ... 240th character
;
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT