Profinet: data output status bad [0x01bc6503, Profinet: data_exchange status quit [0x01bc6531, Profinet: station name error [0x01bc6532 – Lenze E84DxxxxxxxxxR User Manual
Page 64: Message, 0x01bc6531, 0x01bc6503, 0x01bc6501, 0x01bc6502, 0x01bc6532, Communication manual 8400 protec profinet
Communication manual 8400 protec PROFINET
Error messages
Possible causes and remedies
64
L
EDS84DPNET EN 4.0 - 11/2010
PROFINET: Record parameter: Invalid read [0x01bc6501]
PROFINET: Record parameter: Invalid write [0x01bc6502]
PROFINET: Data output status bad [0x01bc6503]
PROFINET: Data_Exchange status quit [0x01bc6531]
PROFINET: Station name error [0x01bc6532]
Response (Lenze setting in bold)
Setting: not possible
None System fault Fault Trouble Quick stop by trouble : Warning locked Warning Information
Cause
Remedy
Invalid parameter read access
Check configuration.
Response (Lenze setting in bold)
Setting: not possible
None System fault Fault Trouble Quick stop by trouble : Warning locked Warning Information
Cause
Remedy
Invalid parameter write access
Check configuration.
Response (Lenze setting in bold)
Setting: not possible
None System fault Fault Trouble Quick stop by trouble : Warning locked Warning Information
Cause
Remedy
Output data invalid.
Connection to Siemens S7 has been interrupted.
Check cables and connections.
Plug in network cable at PROFINET terminal X256 or
X257.
Response (Lenze setting in bold)
Setting:
(; Adjustable response)
:
None System fault ; Fault Trouble ; Quick stop by trouble ; Warning locked Warning ; Information
Cause
Remedy
The data exchange via PROFINET has been terminated.
• See also chapter "
Check cables and connections.
Plug in network cable at PROFINET terminal X256 or
X257.
Response (Lenze setting in bold)
Setting: not possible
None System fault Fault Trouble Quick stop by trouble : Warning locked Warning Information
Cause
Remedy
A station name that is not conform to PROFINET has
been defined.
Change the station name according to the PROFINET
specification:
• 1 or several labels separated by ".".
• Max. length per label: 63 characters
• Max. total length: 240 characters
• Permissible characters: [a ... z], [0 ... 9], [.], [-]
• Labels must not begin or end with [-].
• Prohibited syntax:
–"n.n.n.n" (n = 0 ... 999)
–"port-xyz" (x, y, z = 0 ... 9)
–"port-xyz-abcde" (a, b, c, d, e, x, y, z = 0 ... 9)