Communication manual 8400 protec PROFINET
Error messages
Possible causes and remedies
PROFINET: Internal error [0x01bc6011]
PROFINET: Internal error [0x01bc6100]
PROFINET: Internal error [0x01bc6101]
PROFINET: Invalid parameter set [0x01bc641f]
PROFINET: Error: Lenze setting loaded [0x01bc6420]
PROFINET: Invalid module configuration [0x01bc6430]
Response (Lenze setting in bold)
Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Device is defective.
Send device with error description to Lenze.
Response (Lenze setting in bold)
Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Internal error
Send device with error description to Lenze.
Response (Lenze setting in bold)
Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Internal error
Send device with error description to Lenze.
Response (Lenze setting in bold)
Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Loading of an active parameter set was not possible.
Download application again (including module).
Response (Lenze setting in bold)
Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Access via standard device to parameter set in the
memory module was not successful.
Download application again (including module).
Response (Lenze setting in bold)
Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
A module or submodule does not comply with the
configuration of the Siemens S7 engineering tool.
Check configuration.