Communication manual 8400 protec PROFINET
Commissioning
Setting the station name
5.3
Setting the station name
The station name ...
is required for unambiguous addressing of the Inverter Drive 8400 protec by the IO
controller.
can either be assigned by the IO controller via PROFINET or set manually in the
»Engineer«.
has to be allocated according to the PROFINET specification:
– 1 or several labels separated by ".".
– Max. length per label: 63 characters
– Max. total length: 240 characters
– Permissible characters: [a ... z], [0 ... 9], [.], [-]
– Labels must not begin or end with [-].
Prohibited syntax:
– "n.n.n.n" (n = 0 ... 999)
– "port-xyz" (x, y, z = 0 ... 9)
– "port-xyz-abcde" (a, b, c, d, e, x, y, z = 0 ... 9)
Note!
• The "Node blinking test" PROFINET function, which serves to identify an
accessible device, is supported. The red LED "BUS-ERR" flickers during
• In the event of impermissible settings, the red LED "BUS-ERR" is blinking. In
this case, the Inverter Drive 8400 protec continues to work internally with the
deleted name. Operation on the PROFINET requires a valid station name.
• If the station name is assigned by the IO controller via PROFINET the change
is activated immediately. The current station name is displayed in code
.