4 heat sinking, 5 line (mains) fusing, 6 fuse recommendations – Lenze S94P01B2 User Manual
Page 16: Installation

S94P01B2
14
Installation
NOTE
The ground connection from the filter must be wired to solid earth
ground, not machine ground.
If the end-user is using a CE-approved motor, the AC filter combined with the
recommended motor and encoder cables, is all that is necessary to meet the EMC
directives listed herein. The end user must use the compatible filter to comply with CE
specifications. The OEM may choose to provide alternative filtering that encompasses
the PositionServo 940 drive and other electronics within the same panel. The OEM has
this liberty because CE requirements are for the total system.
3.4
Heat Sinking
The PositionServo 940 drive contains sufficient heat sinking within the specified ambient
operating temperature in their basic configuration. There is no need for additional heat
sinking. However, you must ensure that there is sufficient clearance for proper air
circulation. As a minimum, you must allow an air gap of 25 mm above and below the
drive.
3.5
Line (Mains) Fusing
External line fuses must be installed on all PositionServo drives. Connect the external
line fuse in series with the AC line voltage input. Use fast-acting fuses rated for 250
VAC or 600 VAC (depending on model), and approximately 200% of the maximum
RMS phase current.
3.6
Fuse Recommendations
Type
(1)
AC Line
Input Fuse
(1ш/3ш)
Miniature
Circuit Breaker
(1)
(1ш/3ш)
AC Line
Input Fuse or
Breaker
(2)
(3)
(N. America)
DC Bus Input
Fuse
(4)
Amp Ratings
E94P020S1N
M20/M10
C20/C10
20/10
10
E94P040S1N
M32/M20
C32/C20
30/20
20
E94P020S2F
M20
C20
20
15
E94P040S2F
M20
C20
20
20
E94P080S2F
M32
C32
32
40
E94P100S2F
M40
C40
40
45
E94P020Y2N
M20/M16
C20/C16
20/15
15
E94P040Y2N
M20/M16
C20/C16
20/15
20
E94P080Y2N
M32/M20
C32/C20
30/20
40
E94P100Y2N
M40/M25
C40/C25
40/25
45
E94P120Y2N
M50/M32
C50/C32
50/30
55
E94P020T4N
M10
C10
10
10
E94P040T4N
M10
C10
10
20
E94P050T4N
M16
C16
15
25
E94P060T4N
M20
C20
20
30
(1)
Installations with high fault current due to large supply mains may require a type D circuit breaker.
(2)
UL Class CC or T fast-acting current-limiting type fuses, 200,000 AIC, preferred. Bussman KTK-R, JJN, JJS or equivalent.
(3)
Thermal-magnetic type breakers preferred.
(4)
DC-rated fuses, rated for the applied voltage. Examples Bussman KTM or JJN as appropriate.