13 parameter reference, C01501 | resp. to communication error with mci, C01503 | mci timeout – Lenze E84DGFCT User Manual
Page 66: Parameter reference, In code, C01501, C01501/2, Communication manual 8400 motec ethercat

Communication manual 8400 motec EtherCAT®
Parameter reference
Communication-relevant parameters of the operating system
66
L
EDS84DMOTECAT EN 2.1 - 11/2012
13
Parameter reference
This chapter complements the parameter list and table of attributes in the software
manual and the »Engineer« online help for the Inverter Drive 8400 motec by the
parameters for the EtherCAT communication.
13.1
Communication-relevant parameters of the operating system
This chapter lists the communication-relevant parameters of the 8400 motec operating
system in numerically ascending order.
C01501
C01503
Software manual/»Engineer« online help "Inverter Drives 8400 motec"
Here you will find general information about parameters.
Parameter | Name:
C01501 | Resp. to communication error with MCI
Data type: UNSIGNED_8
Index: 23074
d
= 5A22
h
Configuration of monitoring functions for the Communication Unit
Selection list
0 No response
1 Error
4 Warning locked
Subcodes
Lenze setting
Info
C01501/1
1: Error
Resp. to MCI error 1
• Response to a communication error.
C01501/2
1: Error
Resp. to MCI error 2
• Response to troubled Communication Unit.
;
Read access ; Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C01503 | MCI timeout
Data type: UNSIGNED_16
Index: 23072
d
= 5A20
h
Setting range
(min. value | unit | max. value)
0
ms
1000
Subcodes
Lenze setting
Info
C01503/1
200 ms
MCI timeout
;
Read access ; Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1