Wiring the device modules, For the dip switches that are placed at the front, The node address (labelling "1" ... "64") and – Lenze E94ARNE User Manual
Page 63: Baud rate (labelling "a" ... "d") can be set

Wiring the device modules
Memory modules
l
63
EDK94ARN24 DE/EN/FR/ES/IT 2.1
Baud
CAN Address
O
N
c
d
b
a
64
32
16
8
4
2
1
A
9400CAN003
Fig. 7−6
Arrangement and labelling of the DIP switches
For the DIP switches that are placed at the front
ƒ
the node address (labelling "1" ... "64") and
ƒ
baud rate (labelling "a" ... "d")
can be set.
)
Note!
If all address switches adopt the "OFF" position when the basic device is
switched on, the configurations of codes C00350 (nodes address) and C00351
(baud rate) apply.
Switch the voltage supply of the basic device off and then on again to activate
altered settings.
Setting the node address
The node address of the drive is calculated from the sum of all address switches in the "ON"
position.
Setting the baud rate
d
c
b
a
Baud rate
OFF
ON
ON
OFF
10 kbit/s
OFF
ON
OFF
ON
20 kbit/s
OFF
OFF
ON
ON
50 kbit/s
OFF
OFF
ON
OFF
125 kBit/s
OFF
OFF
OFF
ON
250 kbit/s
OFF
OFF
OFF
OFF
500 kbit/s
ON
ON
ON
OFF
800 kbit/s
OFF
ON
OFF
OFF
1000 kbit/s
OFF
ON
ON
ON
Auto baud