beautypg.com

2 electrical data, Electrical data, Technical data – Lenze E94ARNE User Manual

Page 46: Input data (on the supply side)

background image

Technical data

Electrical data

3

l

46

EDK94ARN24 DE/EN/FR/ES/IT 2.1

3.2

Electrical data

Basis of the data

Mains

Voltage

Voltage range

Frequency range

U

LN

[V]

U

LN

[V]

f [Hz]

3/PE AC

230

180 − 0 % ... 264 + 0 %

45 − 0 % ... 65 + 0 %

3/PE AC

400

320 − 0 % ... 440 + 0 %

45 − 0 % ... 65 + 0 %

3/PE AC

500

400 − 0 % ... 550 + 0 %

45 − 0 % ... 65 + 0 %

Input data (on the supply side)

Voltage

Frequency

Current [A]

Number of

phases

[V]

[Hz]

max. +45 °C



max. +55 °C



E94ARNE0134

In motor mode

230/400/500

50/60

26/26/26

19.5/19.5/19.5

3

In generator mode

230/400/500

50/60

13/13/13

9.8/9.8/9.8

3

E94ARNE0244

In motor mode

230/400/500

50/60

47/47/47

35/35/35

3

In generator mode

230/400/500

50/60

23.5/23.5/23.5

17.6/17.6/17.6

3

 Temperature in the control cabinet

Voltage

Continuous input power

Type

[V]

S

L

[kVA]

E94ARNE0134

In motor mode

230/400/500

10.3/18.0/22.5

In generator mode

230/400/500

5.2/9.0/11.2

E94ARNE0244

In motor mode

230/400/500

18.7/32.5/40.7

In generator mode

230/400/500

9.4/16.3/20.3