beautypg.com

3 technical data, 1 general data and operating conditions, Technical data – Lenze E94ARNE User Manual

Page 44: General data and operating conditions, 3technical data

background image

Technical data

General data and operating conditions

3

l

44

EDK94ARN24 DE/EN/FR/ES/IT 2.1

3

Technical data

3.1

General data and operating conditions

Conformity and approval

Conformity

CE

2006/95/EG

Low−Voltage Directive

Approval

UL

UL 508C

In preparation:
Industrial Control Equipment, File No. 132659

Mains data

Mains types

With earthed

*

neutral

Full usability

The measures described for IT
systems must be observed
and carried out in all systems
(TN, TT and IT) and for all
interconnected modules!

IT systems

Full usability

Noise emission

EN 61800−3

With E94AZMR0xx4SDB mains filter: 6 x 10 m, C2
With E94AZMR0xx4LDB mains filter: 10 x 50 m, C2

Radiation: category C3

Noise immunity (as required in EN 61800−3)

Electrostatic discharge
(ESD)

EN 61000−4−2

8 kV with air discharge,
4 kV with contact discharge to housing

High frequency

Cable−guided

EN 61000−4−6

150 kHz ... 80 MHz, 10 V/m 80% AM (1kHz)

Interference (housing)

EN 61000−4−3

80 MHz ... 1000 MHz, 10 V/m 80% AM (1kHz)

Protection of persons and device protection

Enclosure

EN 60529

IP 20

Not in the wire range of
the terminals on the
motor side

NEMA 250

Protection against contact to
type 1

Insulation resistance

EN 61800−5−1

Overvoltage category III
Derating at and above 2000 m AMSL: overvoltage category II

Isolation of control circuits EN 61800−5−1

Safe mains isolation through double/reinforced insulation.

Short−circuit strength

EN 61800−5−1

DC−bus connection: not short−circuit−proof
Brake resistor connection: full
Control connections: full

Discharge current

EN 61800−5−1

> 3.5 mA

Observe regulations and
safety instructions!

Cyclic mains switching

Cyclic mains switching of five times in five minutes is fully
permissible.