C14041 | epl version, C14042 | current epl device address, C14043 | epl device address selection – Lenze E94AYCEC User Manual
Page 93: C14044 | epl device address sw, C14044, C14042, 10 parameter reference
![background image](/manuals/565769/93/background.png)
Lenze · E94AYCEC Communication module (POWERLINK CN) · Communication Manual · DMS 3.0 EN · 08/2014 · TD17
93
10
Parameter reference
10.3
Parameters of the communication module for slot MXI2
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C14041
C14042
C14043
C14044
Parameter | Name:
C14041 | EPL version
Data type: UNSIGNED_8
Index: 10534 = 0x2926
EPL index: not available
The code describes the version of the POWERLINK communication profile implemented by the communication
module.
The higher-order nibble describes the major version, the lower order nibble describes the minor version. The
implemented value corresponds to the POWERLINK version 2.0.
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14042 | Current EPL device address
Data type: UNSIGNED_8
Index: 10533 = 0x2925
EPL index: 0x1F93.0x01
The code displays the currently valid EPL node address (Node ID).
• The node ID must be unequivocal in the EPL network segment.
Display area
(min. value | unit | max. value)
1
240
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14043 | EPL device address selection
Data type: UNSIGNED_8
Index: 10532 = 0x2924
EPL index: 0x1F93.0x02
The code indicates whether the EPL node address (node ID) has been set via DIP switches at the communication
module or via the software.
• 0: Node ID has been set via software (
• 1: Node ID has been set via DIP switches at the communication module.
Display area
(min. value | unit | max. value)
0
1
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14044 | EPL device address SW
Data type: UNSIGNED_8
Index: 10531 = 0x2923
EPL index: 0x1F93.0x03
This code serves to set the EPL node address (node ID) via the software.
The value "0" (Lenze setting) is not a valid node ID. It serves to activate the setting via the DIP switches.
Setting range
(min. value | unit | max. value)
Lenze setting
1
240 0
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT