C13075
C13078
C13079
Parameter | Name:
C13075 | EPL SDO channel width
Data type: UNSIGNED_16
Index: 11500 = 0x2CEC
EPL index: 0x1F98.0x08
The code defines the maximum user data size of asynchronous frames. Protocol-specific headers for POWERLINK,
UDP/IP and others as well as service-specific headers are to be interpreted as part of the user data.
In the configured state, the C13075 values of all EPL nodes must be identical.
Setting range
(min. value | unit | max. value)
Lenze setting
282
Byte
1500 282 bytes
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13078 | EPL CN: Max. time - MN detection
Data type: UNSIGNED_32
Index: 11497 = 0x2CE9
EPL index: 0x1F99
The code defines the time interval needed for detecting a managing node. If a booting controlled node detects a
managing node during the interval, it changes to NMT_CS_PREOPERATIONAL_1. If not, it changes to "Basic Ethernet
Mode".
Setting range
(min. value | unit | max. value)
Lenze setting
0
μs
4294967295 10000000 μs
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13079 | EPL multi-stage node declaration CN
Data type: UNSIGNED_8
Index: 11496 = 0x2CE8
EPL index: See subcodes
This code indicates in which multiplexed cycle the controlled node is queried. The value entered must not exceed
the value in code
If, for instance, the value "3" is entered in code
, the multiplexed cycle is repeated every three cycles. If now
the value "3" is entered for one node in C13079/x, it is always queried only in the second cycle of the three
multiplexed cycles.
Setting range
(min. value | unit | max. value)
0
Cycles
255
Subcodes
Lenze setting
Info
EPL index
C13079/1
0 cycles
0x1F9B.0x01
...
...
...
C13079/100
0 cycles
0x1F9B.0x64
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT