0x00c88130, 0x00c88131, 0x00c88261 – Lenze E94AYCEC User Manual
Page 58: 0x00c88263, 0x00c88264, 9error messages
![background image](/manuals/565769/58/background.png)
9
Error messages
9.1
Error messages of the communication module
58
Lenze · E94AYCEC Communication module (POWERLINK CN) · Communication Manual · DMS 3.0 EN · 08/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
EPL: Fieldbus watchdog activated [0x00c88130]
EPL: DataExchange exited [0x00c88131]
EPL: Invalid address selected [0x00c88261]
EPL MN: Network has not been started (bootup-1) [0x00c88263]
EPL MN: Not all nodes are in the operational status (bootup-2) [0x00c88264]
Response (Lenze setting printed in bold)
Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked warning Information
Cause
Remedy
Communication module is defective.
Send communication module together with a
description of the fault to Lenze.
Response (Lenze setting printed in bold)
Setting:
/
( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
The POWERLINK data exchange has been terminated.
• Check wiring.
• Plug network cable into POWERLINK terminal X251 or
X252.
Response (Lenze setting printed in bold)
Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
An invalid IP address has been assigned by the managing
node via POWERLINK or set as node ID.
• Ensure that a valid IP address is assigned by the
managing node via POWERLINK.
• Set valid node ID.
Response (Lenze setting printed in bold)
Setting:
/
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
• The Managing Node could not start the POWERLINK
network.
• Not all required nodes were found.
• Check if all nodes are switched on
• Check address setting and wiring.
Response (Lenze setting printed in bold)
Setting:
/
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
The Managing Node could not transfer all nodes into the
"NMT_CS_OPERATIONAL" status via process data
exchange.
Check whether single nodes are in error status.