Monitoring
The communication module provides several monitoring functions. The standard settings can be
changed in the »Engineer« under the Monitoring tab.
For the settings, monitoring responses and monitoring thresholds can be specified. When the
monitoring thresholds are exceeded, the response of the Servo Drive 9400 is specified together with
the POWERLINK-specific monitoring response. The required status is adopted which is additionally
entered into the logbook of the Servo Drive 9400. The setting ’No response’ deactivates the
monitoring function.
Weighted process
The monitoring threshold, for instance, serves to define the number of errors which may occur in
succession. Here, the POWERLINK uses a weighted process which must be considered when the
monitoring threshold is entered:
• As soon as an error occurs, an internal error counter is increased by the value "8".
• As soon as a POWERLINK cycle was successful, the error counter is reduced by the value ’1’.
• Thus 8 faultless transmissions are required after an error has been detected, in order that the
error counter assumes the value "0" again.
Note!
Generally, all set monitoring functions must be reset after they occurred and before they
can be transmitted again since they affect the fieldbus behaviour and the behaviour of
the communication module.