0x00c88283, 0x00c88284, 9error messages – Lenze E94AYCEC User Manual
Page 60
9
Error messages
9.1
Error messages of the communication module
60
Lenze · E94AYCEC Communication module (POWERLINK CN) · Communication Manual · DMS 3.0 EN · 08/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
EPL: MN address assigned double [0x00c88283]
EPL: Internal error [0x00c88284]
Response (Lenze setting printed in bold)
Setting: not possible
No reaction System fault Fault Trouble Quick stop by trouble WarningLocked Warning Information
Cause
Remedy
The address setting of the Managing Node has been
assigned several times (node ID = ’240’).
This node is configured as Managing Node but does not
participate in the frame traffic due to double addressing.
Correct address setting.
Response (Lenze setting printed in bold)
Setting: not possible
No reaction System fault Fault Trouble Quick stop by trouble WarningLocked Warning Information
Cause
Remedy
Internal error.
Send communication module together with a
description of the fault to Lenze.