beautypg.com

Led status displays of the mc-pbs, Communication card ( 48), 10 diagnostics – Lenze PROFIBUS Controller-based Automation User Manual

Page 48

background image

10

Diagnostics

10.2

LED status displays of the MC-PBS communication card

48

Lenze · Controller-based Automation · PROFIBUS® Communication Manual · DMS 4.3 EN · 04/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

10.2

LED status displays of the MC-PBS communication card

[10-2] LED status displays

MC-PBx-001_LED

LED

Colour

State

Description

SYS

Green

On

Communication active

(cyclic data exchange with the PROFIBUS master)

Blinking 5 times per

second (5 Hz)

No communication

(no cyclic data exchange with the PROFIBUS master)

Blinking irregularly

• Starting action: Missing or faulty configuration

• Runtime: Host watchdog time error

Yellow

Blinking once per

second (1 Hz)

The device is in bootstrap loader mode and is waiting for the

firmware download

Blinking 5 times per

second (5 Hz)

The firmware download is executed.

Blinking irregularly

A hardware or severe system error has been detected.

-

Off

No voltage supply or hardware is defective.

ST0

-

Off

No function

ST1

-

Off

No function

ST2

Red

On

The application program (bus-synchronous/device-controlled

communication mode) is no longer synchronous with the bus cycle.

Yellow

On

The slave has received parameter/configuration data from the

PROFIBUS master and is in the "DataExchange" state".

-

Off

No PROFIBUS communication

("DataExchange" state not reached)